          1. Hello! welcomeZhejiang Xikai Electric Co. , Ltd.
            Zhejiang Xikai Electric Co. , Ltd.
            Contact
            Zhejiang Xikai Electric Co. , Ltd.
            Mailbox:wzxikai@wzxikai.com
            Tel:+86 577 61666 016
            address:No.271, Weishiqi Road, Yueqing Economic Development Insuatrial Zone, Yueqing, Zhejiang.

            product list

            Indoor high voltage load switch
            14/5000 Indoor vacuum circuit breaker
            Outdoor vacuum circuit breaker
            Outdoor high voltage load switch
            Outdoor high voltage disconnector
            Outdoor drop fuse
            High voltage current limiting fuse series
            High voltage complete set
            current position:Home>Product Center

            Product Center

              • AB-3S Outdoor Permanent Vacuum Circuit Breaker (Recloser)

              AB-3S Outdoor Permanent Vacuum Circuit Breaker (Recloser)

              AB-3S Outdoor Permanent Vacuum Circuit Breaker (Recloser) adopts vacuum arc extinguishing principle, permanent magnet operating mechanism, integrated micro-processing technology, modern network communication technology and new switch manufacturing materials. Outdoor power distribution equipment with rated voltage of 12kV, 24kV,40.5kV,50Hz three-phase AC. This product is widely used in urban power grids as a break or tie switch, or used in rural power distribution system outdoor substation outlet switch, which can effectively complete the split and load current and short circuit current.

              Technical Information

              Technical Specification

               

               

               

               

              Rated voltage

              kV

              12

              24

              40.5

              Rated frequency

              Hz

              50

              50

              50/60

              Rated current

              A

              630

              630

              1250/1600

              Rated short-circuit breaking current

              kA

              20

              25

              25/31.5

              Rated peak withstand current (peak)

              KA

              50

              63

              63

              Rated short-time withstand current

              kA

              20

              25

              63/80

              Rated short circuit closing current (peak)

              kA

              50

              63

              63/80

              Mechanical life

              Times

              10000

              10000

              10000

              Rated short-circuit breaking current breaking times

              Times

              ≥30

              ≥30

              30

              Power frequency withstand voltage (1min): (wet) (dry) phase, ground / fracture

              kV

              42/48

              52;65/79

              80 95/95

              Lightning impulse withstand voltage (peak) phase to ground, ground / fracture

              kV

              75/85

              125/145

              185

              Secondary circuit 1min power frequency withstand voltage

              kV

              2

              2

              2